Rating of Power Cable
2. Rating of Power Cable Short Circuit Rating It happens frequently that the conductor size necessary for an installation is dictated by its ability to carry short-circuit current rather than sustained current. During a short – circuit, there is a sudden inrush of current for a few cycles followed by a steadier flow of current for a short period until the protection switchgear operators, normally between 0.1-0.3 seconds. Conductor Size and Material Insulation Material Operating Maximum Temperature Short Circuit Rating 120 sq-mm Copper conductor PVC Insulation 70oC 13.80 KA/SEC 120 sq-mm Aluminium conductor PVC Insulation 70oC 9.12 KA/SEC 120 sq-mm Copper conductor PVC Insulation 85oC 12.48 KA/SEC 120 sq-mm Aluminium conductor PVC Insulation 85oC 8.28 KA/SEC Current Carrying Capacity Current carrying capacity is an important aspect is the selection of the optimum size of conductor. Voltage drop and short rating is also very important aspect to ...